Toshiba Blinking Light & Error Codes

How to check your Toshiba code in 30 seconds: Hold TIMER OFF for >10 seconds on wired/diagnostic controllers (or press CHECK with a pin on wireless remotes) to view recorded check codes [01] (newest) through [04] (oldest). Need to check warranty status? Use the Toshiba Serial Age Checker. (Source: Toshiba Air Conditioning Official Check Code & Troubleshooting Manual (PDF) ↗)

Complete Toshiba Fault Code Encyclopedia Table

CodePart AffectedUrgencyPlain-English Meaning & What to Try FirstManual
E04Indoor/Outdoor Serial CircuitHigh — Communication Check CodeSerial communication circuit fault between indoor unit and outdoor inverter unit.
Safe check: Switch circuit breaker OFF per Toshiba safety guidance, wait 5 minutes, and restore power once; persistent E04 requires interconnecting wiring and outdoor I/F board inspection.
Source ↗
P01Indoor Fan MotorModerate — Fan Thermal / LockIndoor fan motor thermal/lock check code.
Safe check: Isolate main breaker and inspect indoor cross-flow fan for obstruction before booking motor replacement.
Source ↗
P10Condensate Float SafetyHigh — Water Overflow ProtectionIndoor float switch high-water-level check code.
Safe check: Keep unit powered off and clear blocked condensate drain hose or lift pump.
Source ↗
H01Outdoor Compressor BreakdownCritical — Compressor OvercurrentOutdoor inverter compressor overcurrent / breakdown protection check code.
Safe check: Set circuit breaker to OFF position per Toshiba manual and schedule qualified service engineer inspection.
Source ↗
H06Low-Pressure ProtectionHigh — Suction Pressure DropOutdoor low-pressure switch / refrigerant circulation protection check code.
Safe check: Confirm service valves are open and test piping joints for R32/R410A leakage.
Source ↗
1AOutdoor Fan Motor & Inverter DriveHigh — Outdoor Unit Shutdown (8x Detection)Outdoor fan drive system error: outdoor fan motor fails to rotate or stops shortly after start due to mechanical lock, motor winding fault (normal phase-to-phase resistance 33.7 ± 1.7 Ω at CN300), hall position-detect fault, or outdoor inverter PCB fan drive failure.
Safe check: Switch off the circuit breaker completely before inspecting the outdoor condenser grille for debris obstructing the propeller blade; have a licensed technician test CN300 motor winding resistance and inverter PCB drive output.
Source ↗
1CRefrigerant Cycle / Sensor FeedbackHigh — Outdoor Compressor Protection StopOutdoor unit protective stop 10 to 60 minutes after startup caused by refrigerant gas shortage or leakage, pulse modulating valve (PMV) coil or strainer restriction, or disconnected/out-of-holder TS suction or TC indoor coil thermistor.
Safe check: Confirm both outdoor service valves are open and indoor air filters are clean; arrange a qualified HVAC technician to verify operating pressure, PMV initialization click on power-up, and TS/TC thermistor seating.
Source ↗
1ECompressor Discharge Temperature (TD)Critical — Thermal Protection Cutoff (>117°C)Compressor discharge pipe temperature exceeded 117°C across 4 consecutive restart cycles (protective speed reduction engages above 103–115°C), typically triggered by R32 refrigerant undercharge from a flare leak, restricted PMV expansion valve, or faulty TD thermistor (64 kΩ at 20°C).
Safe check: Turn off the air conditioner and isolate the main breaker so the compressor cools down; do not force repeated restarts before a technician leak-tests the flare joints and inspects refrigerant charge and PMV coil resistance.
Source ↗
Engineering Reference

Technical Schematic

Toshiba R32 Discharge Pipe Temperature (TD) Protection Bands & 1E Cutoff
Toshiba R32 Discharge Pipe Temperature (TD) Protection Bands & 1E Cutoff① Normal inverter frequency tracking below 96°C; ② Hold & slow frequency step-down band (96–106°C); ③ Aggressive compressor speed reduction band (106–117°C); ④ 117°C hard cutoff logging check code 1E after 4 trips.