Mitsubishi Electric Troubleshooting
Mitsubishi Electric Blinking Light & Error Codes
Complete Mitsubishi Electric Fault Code Encyclopedia Table
| Code | Part Affected | Urgency | Plain-English Meaning & What to Try First | Manual |
|---|---|---|---|---|
| P1 | Indoor Sensor | Moderate — Thermistor Fault | Intake air temperature sensor (RT11 room thermistor) open or short circuit. Technician reference: Technician only: Record LED blink count (1–2 blink pattern) and power-cycle breaker once. Technician tests thermistor resistance (~10 kΩ at 25 °C) and replaces clip-on sensor harness. | Source ↗ |
| P2 | Indoor Coil Sensor | Moderate — Pipe Thermistor | Indoor liquid pipe (TH2) temperature sensor open or short circuit. Technician reference: Technician only: Common cause of Starmex blinking light after 15–30 minutes of operation; requires indoor pipe thermistor replacement. | Source ↗ |
| P8 | Refrigeration Cycle | High — Abnormal Pipe Temp | Abnormal indoor coil pipe temperature (coil fails to drop temperature during compressor cooling call). Technician reference: Technician only: Clean indoor air filters first; check if other rooms on the multi-split cool normally (isolates faulty outdoor LEV expansion valve vs low R32 charge). | Source ↗ |
| P9 | Indoor Condenser/2-Phase Sensor | Moderate — Pipe Thermistor | Indoor two-phase pipe (TH5) heat-exchanger sensor error. Technician reference: Technician only: Turn unit off and book dual-thermistor harness replacement for the affected MSXY/MSY indoor coil. | Source ↗ |
| E6 | Inter-Unit Serial Comms | High — Comms Halted | Indoor/outdoor unit serial signal reception/transmission error (6-time LED blink pattern). Technician reference: Technician only: Check outdoor isolator and main DB breaker; reset power for 5 minutes. Persistent E6 indicates S1-S2-S3 terminal oxidation or outdoor noise-filter/power board fault. | Source ↗ |
| P4 | Condensate Drain Sensor | High — Drain Sensor Fault | Abnormality of indoor drain sensor (DS) or float switch connector CN31/CN4F open (2-time LED blink pattern). Technician reference: Technician only: Turn unit off, clear any water accumulation in the drain pan, and have a technician inspect the drain sensor and CN31/CN4F connector on the indoor controller board. | Source ↗ |
| P5 | Condensate Overflow Safety | High — Water Overflow Stop | Indoor drain overflow protection activated (water level in drain pan reached high float threshold; 2-time LED blink pattern). Technician reference: Technician only: Switch unit OFF immediately to prevent water dripping onto walls/sockets; vacuum-flush the 16 mm PVC drain line and test the condensate drain pump. | Source ↗ |
| P6 | Indoor Evaporator Coil | Moderate — Coil Freeze / Overpressure | Freezing protection in cooling mode or过昇 (over-temperature/pressure) protection in heating mode (3-time LED blink pattern). Technician reference: Technician only: Wash clogged mesh air filters and ensure indoor airflow is not short-cycling; if ice still forms on the coil, check indoor fan motor RPM and refrigerant charge. | Source ↗ |
| LED1-LIT-LED2-1X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Linear Expansion Valve (LEV) & Drain Pump Interlock (LED1 Red Lit / LED2 Yellow 1× Blink) | Critical — Outdoor Unit Does Not Operate (LEV Stepper Coil or Drain Pump Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks once indicates a Linear Expansion Valve (LEV) or condensate drain pump abnormality, preventing outdoor unit startup (Page 8, No. 1). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes; have a licensed technician inspect the outdoor Linear Expansion Valve (LEV) stepper motor connectors and coil winding resistance across all ports, and check any connected SEZ/PEY ducted indoor condensate drain pump circuit per Page 8 (No. 1) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-3X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Compressor Discharge Temperature Thermistor Circuit (LED1 Red Lit / LED2 Yellow 3× Blink) | Critical — Outdoor Unit Does Not Operate (Discharge Temperature Thermistor Open/Short) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 3 times indicates an open or shorted compressor discharge temperature thermistor circuit, preventing outdoor unit operation (Page 8, No. 3). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes and have a licensed technician inspect the compressor discharge temperature thermistor plug on the outdoor control P.C. board and measure the NTC thermistor resistance curve per Page 8 (No. 3) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-5X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Ambient & Heat Exchanger Temperature Thermistor Circuit (LED1 Red Lit / LED2 Yellow 5× Blink) | Critical — Outdoor Unit Does Not Operate (Ambient / Outdoor Heat Exchanger Thermistor Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 5 times indicates an abnormality in the outdoor ambient temperature thermistor or outdoor heat exchanger temperature thermistor, preventing outdoor unit startup (Page 8, No. 5). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and have a technician inspect the outdoor ambient temperature thermistor and outdoor heat exchanger coil thermistor connectors and test their NTC resistance values per Page 8 (No. 5) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-6X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Control P.C. Board Zero Cross Detecting Circuit (Page 8, Table No. 6) | Critical — Outdoor Unit Does Not Operate (LED1 Red Lit / LED2 Yellow 6× Blink) | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit does not operate and LED1 (Red) is lit while LED2 (Yellow) blinks 6 times (Page 8, Table No. 6 — distinct from Table No. 10 / No. 25 12× blink on the outdoor power P.C. board), the fault is in the zero cross detecting circuit on the outdoor control P.C. board. Technician reference: Technician only: Isolate 230V AC power at the outdoor isolator; per Page 8 (Table No. 6) of the Mitsubishi Electric service manual, replace the outdoor control P.C. board. | Source ↗ |
| LED1-LIT-LED2-11X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Inter-Board Serial Communication Bus (LED1 Red Lit / LED2 Yellow 11× Blink) | Critical — Outdoor Unit Does Not Operate or Repeats 3-Minute Stop/Restart Loop (Inter-Board Communication Error) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 11 times indicates a communication error between the outdoor control P.C. board and the outdoor power P.C. board, causing either complete outdoor non-operation (Page 8, Table No. 9: 'Communication error between P.C. boards') or a repeated 3-minute stop-and-restart protection cycle (Page 10, Table No. 24: 'Communication between P.C. boards protection'). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes to discharge the inverter DC bus capacitors, then have a licensed technician inspect the interconnecting ribbon/wire harness between the outdoor control P.C. board and the outdoor power P.C. board per Page 8 (No. 9) and Page 10 (No. 24) of the Mitsubishi Electric service guide ('Check the connecting wire between outdoor control P.C. board and outdoor power P.C. board'). | Source ↗ |
| LED1-LIT-LED2-8X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Current Sensor & Current Sensor Protection (LED1 Red Lit / LED2 Yellow 8× Blink) | Critical — Outdoor Current Sensor Fault (Non-Operating or 3-Minute Auto-Restart Loop) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 8 times indicates a current sensor abnormality on the outdoor power P.C. board, either preventing outdoor startup altogether (Page 8, No. 8) or triggering a repeated 3-minute stop-and-restart current sensor protection loop (Page 10, No. 23). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes and inspect the interconnecting harness between the outdoor control P.C. board and outdoor power P.C. board; if LED1 Lit + LED2 8-blink recurs, replace the outdoor power P.C. board per Page 8 (No. 8) and Page 10 (No. 23) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-12X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Zero Cross Detecting Circuit Lockout (Page 8, Table No. 10) | Critical — Outdoor Unit Does Not Operate (LED1 Red Lit / LED2 Yellow 12× Blink) | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit does not operate at all and LED1 (Red) is lit while LED2 (Yellow) blinks 12 times (Page 8, Table No. 10 — distinct from Page 10 Table No. 25 where the unit repeats a 3-minute restart cycle), the unit has locked out on the zero cross detecting circuit of the outdoor power P.C. board. Technician reference: Technician only: Isolate 230V AC power at the outdoor isolator; per Page 8 (Table No. 10) of the Mitsubishi Electric service manual, replace the outdoor power P.C. board. | Source ↗ |
| LED1-LIT-LED2-14X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Voltage Sensor Circuit (LED1 Red Lit / LED2 Yellow 14× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Power PCB Voltage Sensor Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 14 times indicates a voltage sensor abnormality on the outdoor power P.C. board, preventing outdoor unit operation (Page 8, No. 12). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and verify that incoming 230V 50Hz AC supply voltage at the outdoor terminal block is within specification; if LED1 Lit + LED2 14-blink persists and the outdoor unit does not operate, replace the outdoor power P.C. board per Page 8 (No. 12) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-15X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Inrush / Main Relay Actuation Circuit (LED1 Red Lit / LED2 Yellow 15× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Power PCB Relay Operation Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 15 times indicates a relay operation fault on the outdoor power P.C. board, preventing outdoor unit startup (Page 9, No. 13). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes to allow the DC bus capacitors to discharge, check the wiring harness between the outdoor control P.C. board and outdoor power P.C. board, and if LED1 Lit + LED2 15-blink recurs on power-up, replace the outdoor power P.C. board per Page 9 (No. 13) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-2X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Inverter IPM / Compressor Lock & PAM Module Protection (LED1 Red 2× Blink / LED2 Yellow Off) | High — Outdoor IPM / Compressor Lock Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking twice while LED2 (Yellow) remains unlit indicates IPM protection or compressor lock protection, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 9, No. 14). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and verify that both liquid and gas service stop valves are fully open; if the 3-minute restart loop persists, have a licensed technician reconnect the U/V/W compressor connector, inspect the inverter/compressor windings, and test the power module (PAM module) per Page 9 (No. 14) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-3X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Compressor Discharge Temperature Overheat & LEV Metering Loop (LED1 Red 3× Blink / LED2 Yellow Off) | High — Compressor Discharge Temperature Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 3 times while LED2 (Yellow) remains unlit indicates compressor discharge temperature protection activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 9, No. 15). Technician reference: Technician only: Clear any airflow obstruction around the outdoor condenser coil and verify that all brass stop valves are fully open; if LED1 3-blink with LED2 Off repeats every 3 minutes, have a technician check the R32 refrigerant charge amount, inspect the refrigerant circuit for restrictions or leaks, and test the Linear Expansion Valve (LEV) stepper coils per Page 9 (No. 15) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-4X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Heatsink Fin & P.C. Board Thermal Protection Circuit (LED1 Red 4× Blink / LED2 Yellow Off) | High — Outdoor Fin / P.C. Board Temperature Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 4 times while LED2 (Yellow) remains unlit indicates heatsink fin temperature protection or P.C. board temperature protection, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 9, No. 16). Technician reference: Technician only: Ensure the outdoor condenser ledge has unrestricted intake/discharge ventilation and that the outdoor fan spins freely; if LED1 4-blink with LED2 Off recurs, have a technician inspect the outdoor fan motor and check the refrigerant circuit and R32 refrigerant amount per Page 9 (No. 16) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-5X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor High-Pressure Switch & Compressor Thermal Protector Interlock (LED1 Red 5× Blink / LED2 Yellow Off) | High — High-Pressure / Thermal Protector Cutout & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 5 times while LED2 (Yellow) remains unlit indicates high-pressure protection or compressor thermal protector activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 9, No. 17). Technician reference: Technician only: Switch off the outdoor isolator breaker and check for condenser airflow short-cycling or partially closed brass stop valves; if LED1 5-blink with LED2 Off persists, have a licensed technician inspect the high-pressure switch and thermal protector harness, confirm the discharge temperature thermistor is seated on the compressor, check for R32 refrigerant leaks or overcharge, and test for a locked compressor per Page 9 (No. 17) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-8X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board — Converter Protection (Page 10, Table No. 19) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red 8× Blink / LED2 Yellow Not Lit) | On Mitsubishi Electric Starmex R32 3/4/5-room multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) blinking 8 times and LED2 (Yellow) not lit (Page 10, Table No. 19 — distinct from MXY-2H20VF Page 6 Table No. 15 where 8× Red / Off Yellow indicates current sensor protection), the unit has tripped on converter protection on the outdoor power P.C. board. Safe check: Homeowner: stop using the unit if the fault repeats and arrange inspection by a qualified air-conditioning technician. Record the model and any indicator visible without opening a cover. Do not open electrical covers, touch the fan, measure mains or DC voltage, or replace circuit boards yourself. The linked manufacturer diagnostic checks are for trained technicians. | Source ↗ |
| LED1-9X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power & Control P.C. Boards — Bus-Bar Voltage Protection (Page 10, Table No. 20) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red 9× Blink / LED2 Yellow Not Lit) | On Mitsubishi Electric Starmex R32 3/4/5-room multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) blinking 9 times and LED2 (Yellow) not lit (Page 10, Table No. 20 — distinct from MXY-2H20VF Page 6 Table No. 13 which uses a single inverter P.C. board), the system has triggered DC bus-bar voltage protection. Safe check: Homeowner: stop using the unit if the fault repeats and arrange inspection by a qualified air-conditioning technician. Record the model and any indicator visible without opening a cover. Do not open electrical covers, touch the fan, measure mains or DC voltage, or replace circuit boards yourself. The linked manufacturer diagnostic checks are for trained technicians. | Source ↗ |
| MUY-LED-6X | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Outdoor Thermistor Circuit (Outdoor LED 6-Time Blink / 2.5s OFF) | Critical — Outdoor Unit Does Not Operate (Outdoor Thermistors Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor inverter P.C. board diagnostic LED blinking 6 times with a 2.5-second OFF pause indicates an outdoor thermistors abnormality under the 'Outdoor unit does not operate' symptom class (Page 2, Table No. 2). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and have a licensed technician check the outdoor thermistors (pipe/heat exchanger, discharge, and ambient sensor resistance and board connectors) per Page 2 (Table No. 2: 'Outdoor thermistors — Check outdoor thermistors') of the Mitsubishi Electric service guide. | Source ↗ |
| MUY-LED-11X | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Outdoor Inverter Control System (Outdoor LED 11-Time Blink / 2.5s OFF) | Critical — Outdoor Unit Does Not Operate (Outdoor Control System / Inverter PCB Fault) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor diagnostic LED blinking 11 times with a 2.5-second OFF pause indicates an outdoor control system fault under the 'Outdoor unit does not operate' symptom class (Page 2, Table No. 3). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes to discharge high-voltage capacitors; if the 11-time blink pattern recurs and the outdoor unit does not operate, replace the outdoor inverter P.C. board per Page 2 (Table No. 3: 'Outdoor control system — Replace inverter P.C. board') of the Mitsubishi Electric service guide. | Source ↗ |
| MUY-LED-14X | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Outdoor Stop Valve / Closed Valve Detection (Outdoor LED 14-Time Blink / 2.5s OFF) | Critical — Outdoor Unit Does Not Operate (Stop Valve / Closed Valve Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor inverter P.C. board diagnostic LED blinking 14 times with a 2.5-second OFF pause indicates a stop valve / closed valve abnormality under the 'Outdoor unit does not operate' symptom class (Page 2, Table No. 5). Technician reference: Technician only: Switch off the outdoor isolator breaker immediately so the compressor does not run against a closed line, and have a licensed technician verify that both liquid (Ø6.35 mm) and gas (Ø9.52 mm / Ø12.70 mm) service stop valves are fully open per Page 2 (Table No. 5: 'Stop valve/ Closed valve — Check stop valve') of the Mitsubishi Electric service guide. | Source ↗ |
| MUY-LED-17X | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Outdoor Refrigerant Circuit (Outdoor LED 17-Time Blink / 2.5s OFF) | Critical — Outdoor Unit Does Not Operate (Outdoor Refrigerant System Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor inverter P.C. board diagnostic LED blinking 17 times with a 2.5-second OFF pause indicates an outdoor refrigerant system abnormality under the 'Outdoor unit does not operate' symptom class (Page 2, Table No. 8). Technician reference: Technician only: Switch off the outdoor isolator breaker and have a licensed technician perform the three checks specified in Page 2 (Table No. 8: 'Outdoor refrigerant system abnormality') of the Mitsubishi Electric service guide: (1) check for a gas leak in a connecting pipe etc., (2) check the stop valve, and (3) check the outdoor refrigerant circuit. | Source ↗ |
| MUY-LED-8X-RESTART | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Compressor Synchronous Drive Circuit (Outdoor LED 8-Time Blink / 2.5s OFF Restart Loop) | High — Outdoor Unit Stops and Restarts 3 Minutes Later Repeatedly (Compressor Synchronous Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor diagnostic LED blinking 8 times (2.5 seconds OFF) while the outdoor unit repeatedly stops and restarts 3 minutes later indicates a compressor synchronous abnormality (Page 3, Table No. 13). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes to discharge high-voltage capacitors, then have a licensed technician reconnect the compressor lead connector and check the inverter P.C. board and compressor windings per Page 3 (Table No. 13: 'Compressor synchronous abnormality — Reconnect connector of compressor. / Check inverter/ compressor.') of the Mitsubishi Electric service guide. | Source ↗ |
| IND-BLINK-1X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Miswiring or Serial Signal (Table No. 1) | High — Indoor & Outdoor Units Do Not Operate (1-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 1 time (Page 1, Table No. 1), the system has detected an S1/S2/S3 interconnect miswiring or serial signal communication abnormality. Technician reference: Technician only: Per Page 1 (Table No. 1) of the official Mitsubishi Electric Starmex error code manual, isolate 230V AC power and check for S1/S2/S3 interconnecting cable miswiring and serial signal error between the indoor and outdoor terminal blocks. | Source ↗ |
| IND-BLINK-2X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Indoor Coil & Room Temperature Thermistors (Table No. 2) | Medium — Indoor & Outdoor Units Do Not Operate (2-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 2 times (Page 1, Table No. 2), the system has detected an open or shorted indoor coil thermistor or room temperature thermistor. Technician reference: Technician only: Per Page 1 (Table No. 2) of the official Mitsubishi Electric Starmex error code manual, isolate power and check both the indoor coil thermistor and room temperature thermistor resistance and PCB connector seating. | Source ↗ |
| IND-BLINK-3X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Indoor Cross-Flow Fan Motor (Table No. 3) | High — Indoor & Outdoor Units Do Not Operate (3-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 3 times (Page 1, Table No. 3), the indoor controller has detected an indoor fan motor rotation or feedback abnormality. Technician reference: Technician only: Per Page 1 (Table No. 3) of the official Mitsubishi Electric Starmex error code manual, switch off the circuit breaker, verify that the indoor blower wheel rotates freely without obstruction, and check the indoor fan motor winding and hall-sensor harness. | Source ↗ |
| IND-BLINK-4X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Indoor Electronic Control System (Table No. 4) | High — Indoor & Outdoor Units Do Not Operate (4-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 4 times (Page 1, Table No. 4), the system has detected an indoor electronic control system fault. Technician reference: Technician only: Per Page 1 (Table No. 4) of the official Mitsubishi Electric Starmex error code manual, isolate 230V AC power for 5 minutes and replace the indoor electronic control P.C. board if the 4-time blink persists. | Source ↗ |
| MUY-LED-12X-FAN | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Outdoor Condenser Fan Motor Drive (Outdoor LED 12-Time Blink / 2.5s OFF Restart Loop) | High — Outdoor Unit Stops and Restarts 3 Minutes Later Repeatedly (Outdoor Fan Motor Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor diagnostic LED blinking 12 times (2.5 seconds OFF) while the outdoor unit repeatedly stops and restarts 3 minutes later indicates an outdoor fan motor fault (Page 3, Table No. 14). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes, visually verify through the condenser grille that no debris obstructs the propeller fan blade, and have a licensed technician perform the two checks in Page 3 (Table No. 14: 'Outdoor fan motor') of the Mitsubishi Electric service guide: (1) check the outdoor fan motor and (2) check the inverter P.C. board. | Source ↗ |
| IND-BLINK-5X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Outdoor Power System (Table No. 5) | High — Indoor & Outdoor Units Do Not Operate (5-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 5 times (Page 1, Table No. 5), the system has detected an outdoor power system abnormality. Technician reference: Technician only: Per Page 1 (Table No. 5) of the official Mitsubishi Electric Starmex error code manual: (1) check the outdoor inverter P.C. board and compressor, and (2) check that both outdoor liquid and gas stop valves are fully open. | Source ↗ |
| IND-BLINK-6X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Outdoor Thermistors (Table No. 6) | Medium — Indoor & Outdoor Units Do Not Operate (6-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 6 times (Page 1, Table No. 6), the system has detected an outdoor thermistor abnormality. Technician reference: Technician only: Per Page 1 (Table No. 6) of the official Mitsubishi Electric Starmex error code manual, isolate 230V AC power and check the outdoor thermistors (discharge, heatsink fin, coil, and ambient NTC thermistor resistance and PCB connector pins). | Source ↗ |
| IND-BLINK-7X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Outdoor Control System (Table No. 7) | High — Indoor & Outdoor Units Do Not Operate (7-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 7 times (Page 1, Table No. 7), the system has detected an outdoor electronic control system abnormality. Technician reference: Technician only: Per Page 1 (Table No. 7) of the official Mitsubishi Electric Starmex error code manual, isolate 230V AC power and replace the outdoor inverter P.C. board or the outdoor electronic control P.C. board. | Source ↗ |
| MUY-LED-10X-RESTART | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Compressor U/V/W Phase Current Sensing (Outdoor LED 10-Time Blink / 2.5s OFF Restart Loop) | High — Outdoor Unit Stops and Restarts 3 Minutes Later Repeatedly (Each Phase Current of Compressor Fault) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor diagnostic LED blinking 10 times (2.5 seconds OFF) while the outdoor unit repeatedly stops and restarts 3 minutes later indicates an abnormality in each phase current of the compressor (Page 3, Table No. 15). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes to discharge high-voltage capacitors, then have a licensed technician check the inverter P.C. board and compressor phase windings/lead harness per Page 3 (Table No. 15: 'Each phase current of compressor — Check inverter/compressor.') of the Mitsubishi Electric service guide. | Source ↗ |
| MUY-LED-13X-RESTART | MUY-GP10VF / 13VF / 18VF / 20VF / 24VF Single-Split Inverter DC Bus-Bar Voltage Circuit (Outdoor LED 13-Time Blink / 2.5s OFF Restart Loop) | High — Outdoor Unit Stops and Restarts 3 Minutes Later Repeatedly (DC Bus-Bar Voltage Abnormality) | On Mitsubishi Electric Starmex R32 MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, and MUY-GP24VF single-split outdoor condensing units, the outdoor diagnostic LED blinking 13 times (2.5 seconds OFF) while the outdoor unit repeatedly stops and restarts 3 minutes later indicates a DC bus-bar voltage abnormality, which on MUY-GP24VF also occurs during an instantaneous power voltage drop / short-time power failure (Page 3, Table No. 16). Technician reference: Technician only: Verify that incoming 230V 50Hz AC power supply at the outdoor isolator is stable (especially on MUY-GP24VF after a momentary voltage dip) and have a licensed technician check the power supply, inverter P.C. board, and compressor per Page 3 (Table No. 16: 'Bus-bar voltage (DC) — Check of power supply. (MUYGP24) / Check inverter/compressor') of the Mitsubishi Electric service guide. | Source ↗ |
| IND-BLINK-8X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Other Abnormality / Stop Valve & Recall Check (Table No. 8) | High — Indoor & Outdoor Units Do Not Operate (8-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 8 times (Page 1, Table No. 8), the system has detected an outdoor stop-valve or other refrigerant/outdoor abnormality requiring outdoor failure-mode recall. Technician reference: Technician only: Per Page 1 (Table No. 8) of the official Mitsubishi Electric Starmex error code manual: (1) check that both outdoor liquid and gas stop valves are fully open, and (2) confirm the abnormality in detail using the failure mode recall function for the outdoor unit. | Source ↗ |
| IND-BLINK-9X | Mitsubishi Electric Starmex R32 Indoor Wall-Mounted Units (MSXY-FP10/13/18/20/24VG & MSY-GP10/13/18/20/24VF) — Outdoor Control System LED Inspection (Table No. 9) | High — Indoor & Outdoor Units Do Not Operate (9-Time Indoor Operation Lamp Blink) | On Mitsubishi Electric Starmex R32 indoor wall-mounted units (MSXY-FP10, 13, 18, 20, 24VG / MSY-GP10, 13, 18, 20, 24VF), when both the indoor unit and outdoor unit do not operate and the indoor Operation indicator lamp blinks 9 times (Page 1, Table No. 9), the system is flagging an outdoor control system abnormality that must be pinpointed on the outdoor board LEDs. Technician reference: Technician only: Per Page 1 (Table No. 9) of the official Mitsubishi Electric Starmex error code manual, check the blinking pattern of the diagnostic LED on the outdoor inverter P.C. board or the outdoor electronic control P.C. board. | Source ↗ |
| MUY-LED-16X | MUY-GP10/13/18/20/24VF Outdoor Inverter P.C. Board — Pipe Temperature Detection (Table No. 7) | High — Outdoor Unit Does Not Operate (16-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10VF, MUY-GP13VF, MUY-GP18VF, MUY-GP20VF, MUY-GP24VF), an outdoor inverter P.C. board LED blinking 16 times with 2.5 seconds OFF after failure-mode recall (Symptom: "Outdoor unit does not operate", Page 2, Table No. 7) indicates a pipe temperature detection fault on the outdoor inverter P.C. board. Technician reference: Technician only: Switch off the 230V AC isolator before opening the MUY-GP outdoor service panel; per Page 2 (Table No. 7) of the official Mitsubishi Electric Starmex error code manual, replace the outdoor inverter P.C. board. | Source ↗ |
| MUY-LED-2X-RESTART | MUY-GP10/13/18/20/24VF Outdoor Compressor Overcurrent Protection (Table No. 9) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (2-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), when the outdoor unit stops and restarts 3 minutes later repeatedly while the outdoor LED blinks 2 times with 2.5 seconds OFF (Page 3, Table No. 9), the outdoor inverter has tripped on overcurrent protection. Technician reference: Technician only: Isolate 230V AC power and follow the three official Page 3 (Table No. 9) service checks: (1) reconnect the compressor lead connector securely, (2) check the outdoor inverter P.C. board and compressor windings, and (3) check that both liquid and gas stop valves are fully open. | Source ↗ |
| MUY-LED-3X-RESTART | MUY-GP10/13/18/20/24VF Outdoor Discharge Temperature Overheat Protection & LEV (Table No. 10) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (3-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), when the outdoor unit stops and restarts 3 minutes later repeatedly while the outdoor LED blinks 3 times with 2.5 seconds OFF (Page 3, Table No. 10 — distinct from Table No. 18 where the outdoor unit continues operating), the unit has tripped on discharge temperature overheat protection. Technician reference: Technician only: Confirm both outdoor stop valves are open and condenser airflow is unobstructed; per Page 3 (Table No. 10) of the Mitsubishi Electric service manual, check the refrigerant circuit and R32 refrigerant amount, and inspect the outdoor linear expansion valve (LEV) coil and stepper drive. | Source ↗ |
| MUY-LED-4X-RESTART | MUY-GP10/13/18/20/24VF Outdoor Fin Temperature / P.C. Board Temperature Thermistor Overheat Protection (Table No. 11) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (4-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), when the outdoor unit stops and restarts 3 minutes later repeatedly while the outdoor LED blinks 4 times with 2.5 seconds OFF (Page 3, Table No. 11 — distinct from Table No. 19 where the outdoor unit continues operating), the inverter has tripped on heatsink fin temperature / P.C. board temperature thermistor overheat protection. Technician reference: Technician only: Per Page 3 (Table No. 11) of the Mitsubishi Electric service manual: (1) check around the outdoor unit for obstructions, (2) check the outdoor unit air passage and clean blocked condenser fins, and (3) check the outdoor condenser fan motor. | Source ↗ |
| MUY-LED-5X-RESTART | MUY-GP10/13/18/20/24VF Outdoor High Pressure Protection Circuit (Table No. 12) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (5-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), when the outdoor unit stops and restarts 3 minutes later repeatedly while the outdoor LED blinks 5 times with 2.5 seconds OFF (Page 3, Table No. 12 — distinct from Table No. 20 where the outdoor unit continues operating), the unit has tripped on high pressure protection. Technician reference: Technician only: Per Page 3 (Table No. 12) of the Mitsubishi Electric service manual: (1) check the refrigerant circuit and R32 refrigerant amount (guarding against overcharge or non-condensables), and (2) check that both liquid and gas stop valves are fully open. | Source ↗ |
| LED1-6X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Compressor Pre-Heating Protection Circuit (LED1 Red 6× Blink / LED2 Yellow Off) | High — Compressor Pre-Heating Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 6 times while LED2 (Yellow) remains unlit indicates pre-heating protection activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 10, No. 18). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and have a licensed technician inspect and reconnect the U/V/W compressor lead connector, test compressor winding continuity/insulation, and check the outdoor power module per Page 10 (No. 18) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-11X-LED2-OFF | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Ambient Temperature Sensing & Low Outside Temperature Cooling Protection (LED1 Red 11× Blink / LED2 Yellow Off) | Moderate — Low Outside Temperature Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 11 times while LED2 (Yellow) remains unlit indicates low outside temperature protection in cooling mode, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 10, No. 21). Technician reference: Technician only: In tropical Singapore ambient conditions (~24°C–35°C), low outside temperature cooling protection should never trigger unless the outdoor ambient temperature thermistor is drifted/shorted or cold discharge air is recirculating directly onto the sensor; have a technician inspect and test the outdoor ambient temperature thermistor per Page 10 (No. 21) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-13X-LED2-OFF | MXY-2H20VF / MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Condenser Fan Motor (Page 6 No. 14 & Page 10 No. 22) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red 13× Blink / LED2 Yellow Not Lit) | Across all Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-2H20VF on Page 6 Table No. 14; MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG on Page 10 Table No. 22), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) blinking 13 times and LED2 (Yellow) not lit, the outdoor DC fan motor has tripped on rotation or feedback abnormality. Safe check: Homeowner: stop using the unit if the fault repeats and arrange inspection by a qualified air-conditioning technician. Record the model and any indicator visible without opening a cover. Do not open electrical covers, touch the fan, measure mains or DC voltage, or replace circuit boards yourself. The linked manufacturer diagnostic checks are for trained technicians. | Source ↗ |
| MXY2H-LED1-LIT-LED2-17X | MXY-2H20VF Outdoor Refrigerant Circuit, Connecting Pipe & Stop Valve / LEV Monitor (Page 5, No. 7) | High — Outdoor Refrigerant System Abnormality Lockout (LED1 Red Lit + LED2 Yellow 17-Time Blink) | Official Mitsubishi Electric Starmex Multi-Split Error Code Chart (MXY-2H20VF Outdoor Unit, Page 5, Item 7): 'Outdoor refrigerant system abnormality' indicated when the outdoor unit does not operate and outdoor control board LED1 (Red) stays continuously lit while LED2 (Yellow) blinks 17 times. Caused by a refrigerant gas leak in a connecting pipe, a closed or partially closed outdoor stop valve, a defective Linear Expansion Valve (LEV), or a restriction in the outdoor refrigerant circuit. Technician reference: Technician only: Switch off the 15A/20A double-pole isolator breaker and do not repeatedly restart the compressor. Have a licensed technician verify with a hex key that both outdoor liquid and gas stop valves are fully open, inspect flare joints for R32 refrigerant oil traces, test LEV stepper coil continuity, and check manifold operating pressures. | Source ↗ |
| MXY2H-LED1-8X-LED2-OFF | MXY-2H20VF Outdoor Inverter P.C. Board Current Sensor Circuit (Page 6, No. 15) | High — 3-Minute Stop/Restart Loop: Current Sensor Protection (LED1 Red 8-Time Blink + LED2 Yellow Off) | Official Mitsubishi Electric Starmex Multi-Split Error Code Chart (MXY-2H20VF Outdoor Unit, Page 6, Item 15): 'Current sensor protection' where the outdoor unit stops and restarts 3 minutes later repeatedly while outdoor LED1 (Red) blinks 8 times and LED2 (Yellow) remains unlit. Triggered by a faulty current-sensing shunt or current transformer circuit on the MXY-2H20VF outdoor inverter P.C. board. Technician reference: Technician only: Turn off the outdoor isolator breaker for 5 minutes to discharge the inverter DC bus and test a single restart. If the 3-minute stop/restart cycle with an 8-time Red LED1 blink persists, per Mitsubishi Electric's service chart, a licensed technician must replace the outdoor inverter P.C. board. | Source ↗ |
| MXY2H-LED1-10X-LED2-OFF | MXY-2H20VF Outdoor Inverter Compressor Drive & Stop Valve Circuit (Page 6, No. 16) | High — 3-Minute Stop/Restart Loop: Compressor Drive Protection (LED1 Red 10-Time Blink + LED2 Yellow Off) | Official Mitsubishi Electric Starmex Multi-Split Error Code Chart (MXY-2H20VF Outdoor Unit, Page 6, Item 16): 'Compressor' protection where the outdoor unit stops and restarts 3 minutes later repeatedly while outdoor LED1 (Red) blinks 10 times and LED2 (Yellow) remains unlit. Caused by a loose compressor U/V/W lead connector, an outdoor inverter P.C. board or twin-rotary compressor winding fault, or a closed outdoor stop valve. Technician reference: Technician only: Isolate mains power and wait 5 minutes for high-voltage capacitor discharge. Have a qualified technician verify that both outdoor liquid and gas stop valves are fully open, reseat the 3-phase U/V/W compressor harness connector, and test compressor winding resistance and inverter P.C. board phase output. | Source ↗ |
| MXY2H-LED1-4X-LED2-OFF | MXY-2H20VF Outdoor Inverter Heatsink Fin / P.C. Board Thermal Protection (LED1 Red 4× Blink / LED2 Yellow Off) | High — Outdoor Fin / PCB Over-Temperature Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 4 times while LED2 (Yellow) remains unlit indicates fin temperature protection or P.C. board temperature protection activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle. Technician reference: Technician only: Switch off the aircon isolator breaker for 5 minutes and inspect the outdoor condenser coil fins and rear/side air intake clearance (minimum 100 mm rear/left and 500 mm front) for blockage or lint; if the 4-blink LED1 pattern recurs, have a technician check the outdoor fan motor and refrigerant charge per Page 6 (No. 11) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-5X-LED2-OFF | MXY-2H20VF Outdoor High-Pressure Protection Circuit (LED1 Red 5× Blink / LED2 Yellow Off) | High — High Refrigerant Head Pressure Trip & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 5 times while LED2 (Yellow) remains unlit indicates high-pressure protection trip on the R32 refrigerant circuit, causing the outdoor unit to stop and repeat a 3-minute restart cycle. Technician reference: Technician only: Confirm that all outdoor liquid and gas service stop valves are fully open and that the outdoor condenser coil has unobstructed airflow; if LED1 5-blink repeats, schedule an HVAC technician to verify R32 refrigerant charge weight (1.22 kg factory pre-charge) and check for refrigerant circuit restriction per Page 6 (No. 12) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-13X-LED2-OFF | MXY-2H20VF Outdoor DC Fan Motor Drive & Feedback Circuit (LED1 Red 13× Blink / LED2 Yellow Off) | High — Outdoor Condenser Fan Motor Fault & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 13 times while LED2 (Yellow) remains unlit indicates an outdoor fan motor abnormality, causing the outdoor unit to stop and repeat a 3-minute restart cycle. Technician reference: Technician only: Isolate mains power at the outdoor breaker, wait 5 minutes for inverter DC bus capacitors to discharge, and visually check that the outdoor propeller fan is free of foreign debris; if the fan blade spins freely by hand but LED1 13-blink persists on restart, have a technician test the outdoor DC fan motor harness and winding resistance per Page 6 (No. 14) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-7X | MXY-2H20VF Outdoor Inverter P.C. Board Nonvolatile Memory (EEPROM) Data (LED1 Red Lit / LED2 Yellow 7× Blink) | Critical — Outdoor Unit Does Not Operate (EEPROM Data Fault) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 7 times indicates a nonvolatile memory data fault on the outdoor inverter P.C. board, preventing outdoor unit operation (Page 5, No. 6). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and restore power to check if the EEPROM read fault clears; if the outdoor unit still does not operate and LED1 Lit + LED2 7-blink persists, have an authorized technician replace the outdoor inverter P.C. board per Page 5 (No. 6) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-9X-LED2-OFF | MXY-2H20VF Outdoor Inverter DC Bus-Bar Voltage Protection Circuit (LED1 Red 9× Blink / LED2 Yellow Off) | High — Bus-Bar Voltage Protection & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 9 times while LED2 (Yellow) remains unlit indicates bus-bar voltage protection activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 6, No. 13). Technician reference: Technician only: Verify that the incoming single-phase 230V 50Hz AC supply voltage is stable and free of sags or surges; if mains voltage is normal and the LED1 9-blink 3-minute restart loop continues, have a technician replace the outdoor inverter P.C. board per Page 6 (No. 13) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-8X-LED2-LIT | MXY-2H20VF Outdoor AC/DC Converter Protection Circuit (LED1 Red 8× Blink / LED2 Yellow Lit) | Moderate — Active Converter Protection Control During Outdoor Operation | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 8 times while LED2 (Yellow) remains continuously lit while the outdoor unit operates indicates active converter protection triggered by power supply voltage abnormality or converter circuit degradation (Page 7, No. 22). Technician reference: Technician only: Have a qualified technician measure the incoming 230V AC supply voltage under load at the outdoor terminal block; if supply voltage is within tolerance and LED1 8-blink + LED2 Lit persists, replace the outdoor inverter P.C. board per Page 7 (No. 22) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-1X | MXY-2H20VF Outdoor Linear Expansion Valve (LEV) & Drain Pump Circuit (LED1 Red Lit / LED2 Yellow 1× Blink) | Critical — Outdoor Unit Does Not Operate (LEV / Drain Pump Fault) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks once indicates an abnormality in the Linear Expansion Valve (LEV) or optional drain pump circuit, preventing outdoor unit operation (Page 5, No. 1). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and inspect the outdoor LEV stepper motor coil connectors and optional indoor drain pump float/wiring (if fitted with SEZ/PEY ducted indoor units); have a qualified technician test LEV coil resistance per Page 5 (No. 1) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-2X | MXY-2H20VF Outdoor Power System, Inverter & Compressor Drive (LED1 Red Lit / LED2 Yellow 2× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Power / Compressor Lockout) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks twice indicates an outdoor power system abnormality across the compressor connecting wire, inverter module, compressor windings, or closed service stop valve, preventing outdoor unit operation (Page 5, No. 2). Technician reference: Technician only: Confirm that both outdoor liquid and gas service stop valves are fully open, then isolate AC mains power for 5 minutes before having a licensed technician inspect the U/V/W compressor lead terminations, compressor winding resistance, and inverter P.C. board per Page 5 (No. 2) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-4X | MXY-2H20VF Outdoor Fin Temperature & P.C. Board Temperature Thermistor Circuit (LED1 Red Lit / LED2 Yellow 4× Blink) | Critical — Outdoor Unit Does Not Operate (Fin / PCB Thermistor Fault) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 4 times indicates an open or shorted outdoor fin temperature thermistor or inverter P.C. board temperature thermistor, preventing outdoor unit operation (Page 5, No. 4). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes and have a technician inspect the outdoor heatsink fin thermistor sensor plug and measure thermistor resistance; if the board-mounted temperature sensor is defective, replace the outdoor inverter P.C. board per Page 5 (No. 4) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-3X | MXY-2H20VF Outdoor Compressor Discharge Temperature Thermistor Circuit (LED1 Red Lit / LED2 Yellow 3× Blink) | Critical — Outdoor Unit Does Not Operate (Discharge Thermistor Fault) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 3 times indicates an open or shorted outdoor compressor discharge temperature thermistor, preventing outdoor unit operation (Page 5, No. 3). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes and have a qualified technician inspect the discharge temperature thermistor clip on the compressor discharge pipe, check the thermistor connector on the outdoor inverter P.C. board, and measure thermistor resistance against the temperature-resistance curve per Page 5 (No. 3) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-LIT-LED2-5X | MXY-2H20VF Outdoor Ambient & Heat Exchanger Temperature Thermistor Circuit (LED1 Red Lit / LED2 Yellow 5× Blink) | Critical — Outdoor Unit Does Not Operate (Ambient / Heat Exchanger Thermistor Fault) | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 5 times indicates an open or shorted outdoor ambient temperature thermistor or outdoor heat exchanger temperature thermistor, preventing outdoor unit operation (Page 5, No. 5). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and have an HVAC technician inspect the outdoor ambient air thermistor and outdoor condenser coil thermistor plugs on the inverter P.C. board and test both thermistors with a multimeter per Page 5 (No. 5) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-2X-LED2-OFF | MXY-2H20VF Outdoor Inverter Compressor Overcurrent Protection (LED1 Red 2× Blink / LED2 Yellow Off) | High — Outdoor Overcurrent Trip & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking twice while LED2 (Yellow) remains unlit indicates an overcurrent trip in the inverter/compressor power circuit, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 6, No. 9). Technician reference: Technician only: Confirm that both outdoor liquid and gas service stop valves are fully open, then isolate mains power for 5 minutes and have a technician reconnect and inspect the compressor lead connector, test compressor phase windings for short/ground faults, and check the outdoor inverter P.C. board per Page 6 (No. 9) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-3X-LED2-OFF | MXY-2H20VF Outdoor Compressor Discharge Temperature Protection Circuit (LED1 Red 3× Blink / LED2 Yellow Off) | High — Outdoor Discharge Overheat Trip & 3-Minute Auto-Restart Loop | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 3 times while LED2 (Yellow) remains unlit indicates compressor discharge temperature protection activation, causing the outdoor unit to stop and repeat a 3-minute restart cycle (Page 6, No. 10). Technician reference: Technician only: Confirm that both outdoor liquid and gas service stop valves are fully open, then switch off the isolator breaker and have a licensed HVAC technician check the R32 refrigerant charge amount (1.20 kg factory pre-charge), inspect the refrigerant circuit for restriction or leakage, and test the Linear Expansion Valve (LEV) per Page 6 (No. 10) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-3X-LED2-LIT | MXY-2H20VF Outdoor Active Discharge Temperature Frequency-Drop Protection (LED1 Red 3× Blink / LED2 Yellow Lit) | Moderate — Active Discharge Temperature Protection During Outdoor Operation | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 3 times while LED2 (Yellow) remains continuously lit while the outdoor unit operates indicates active discharge temperature protection modulating compressor frequency (Page 7, No. 19). Technician reference: Technician only: Have a qualified technician inspect the R32 refrigerant circuit and refrigerant charge level, test the Linear Expansion Valve (LEV) stepper motor coils for proper superheat metering, and check the outdoor discharge and heat-exchanger thermistors per Page 7 (No. 19) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-4X-LED2-LIT | MXY-2H20VF Outdoor Low Discharge Temperature / Liquid Floodback Protection (LED1 Red 4× Blink / LED2 Yellow Lit) | Moderate — Active Low Discharge Temperature Protection During Outdoor Operation | On Mitsubishi Electric Starmex R32 MXY-2H20VF multi-split outdoor condensers, LED1 (Red) blinking 4 times while LED2 (Yellow) remains continuously lit while the outdoor unit operates indicates low discharge temperature protection triggered by excessive liquid refrigerant flow or LEV metering error (Page 7, No. 20). Technician reference: Technician only: Have an HVAC technician inspect the outdoor Linear Expansion Valve (LEV) for a stuck-open valve needle or miswired stepper coil plug, and verify the refrigerant circuit and R32 charge weight per Page 7 (No. 20) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-5X-LED2-LIT | MXY-2H20VF Outdoor Condenser Cooling High-Pressure Frequency Modulation Control (LED1 Red 5× Blink / LED2 Yellow Lit) | Low — Protective Operating State (Outdoor Unit Operates While Modulating High Pressure) | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, LED1 (Red) blinking 5 times while LED2 (Yellow) remains continuously lit indicates cooling high-pressure protection while the outdoor unit continues operating (Page 7, No. 21). Mitsubishi Electric notes this symptom does not mean a product malfunction, but signals elevated condensing pressure. Technician reference: Technician only: Per Page 7 (No. 21) of the Mitsubishi Electric service guide, clean clogged indoor air filters, check whether indoor or outdoor air circulation is short-cycled on a recessed balcony or aircon ledge, and have a technician verify R32 refrigerant charge if the indication persists. | Source ↗ |
| MXY2H-LED1-7X-LED2-LIT | MXY-2H20VF Indoor Evaporator Freeze-Prevention Temperature Control (LED1 Red 7× Blink / LED2 Yellow Lit) | Low — Normal Anti-Freeze Evaporating Temperature Control While Operating | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, LED1 (Red) blinking 7 times while LED2 (Yellow) remains continuously lit indicates cooling evaporating temperature protection while the outdoor unit continues operating (Page 7, No. 23). Mitsubishi Electric explicitly states this symptom does not indicate any abnormality of the product. Technician reference: Technician only: Verify that indoor fan coil mesh filters and blower wheels are clean so indoor airflow across the evaporator coil is not restricted; no PCB or compressor replacement is required for normal evaporating temperature protection per Page 7 (No. 23). | Source ↗ |
| MXY2H-LED1-9X-LED2-LIT | MXY-2H20VF Outdoor Inverter Diagnostic Check Mode (LED1 Red 9× Blink / LED2 Yellow Lit) | Moderate — Active Inverter Check Mode During Outdoor Unit Operation | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, LED1 (Red) blinking 9 times while LED2 (Yellow) remains continuously lit indicates that the outdoor inverter P.C. board is executing inverter check mode while the outdoor unit operates (Page 7, No. 24). Technician reference: Technician only: Observe whether the unit transitions to normal operation (both LED1 Red and LED2 Yellow continuously lit per Page 7, No. 25); if the unit trips into a non-operating fault, inspect the compressor lead connector and test the outdoor inverter P.C. board and compressor windings. | Source ↗ |
| MXY2H-LED1-OFF-LED2-OFF | MXY-2H20VF Outdoor Compressor Thermal Protector, Stop Valve & Discharge Thermistor Interlock (LED1 Red Not Lit / LED2 Yellow Not Lit) | Critical — Outdoor Unit Does Not Operate (Thermal Protector / Closed Stop Valve / Locked Compressor) | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, when the outdoor unit does not operate and both LED1 (Red) and LED2 (Yellow) remain unlit (Page 5, No. 8), the unit has tripped on thermal protector protection, a faulty thermal protector, a discharge temperature thermistor disconnected from the compressor, an indoor/outdoor refrigerant leak, a partially closed stop valve, or a locked compressor. Technician reference: Technician only: Switch off the outdoor isolator breaker and verify that both liquid and gas stop valves are fully open; have a licensed technician check that the discharge temperature thermistor is clipped firmly onto the compressor, test the compressor thermal protector continuity, check for R32 refrigerant leaks, and inspect the compressor windings per Page 5 (No. 8) of the Mitsubishi Electric service guide. | Source ↗ |
| MXY2H-LED1-1X-LED2-LIT | MXY-2H20VF Outdoor Inverter Primary & Secondary Current Protection Modulation (LED1 Red 1× Blink / LED2 Yellow Lit) | Low — Protective Operating State (Primary / Secondary Current Modulation While Operating) | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, LED1 (Red) blinking once while LED2 (Yellow) remains continuously lit indicates primary current protection or secondary current protection while the outdoor unit continues operating (Page 7, No. 17). Mitsubishi Electric notes these symptoms do not mean a product malfunction. Technician reference: Technician only: Per Page 7 (No. 17) of the Mitsubishi Electric service guide, clean clogged indoor air filters, verify that indoor or outdoor unit air circulation is not short-cycled, and check whether the R32 refrigerant charge is low. | Source ↗ |
| MXY2H-LED1-2X-LED2-LIT | MXY-2H20VF Indoor Heat Exchanger Anti-Icing Defrost Control in Cooling Mode (LED1 Red 2× Blink / LED2 Yellow Lit) | Low — Protective Operating State (Defrosting in Cooling Mode While Operating) | On the Mitsubishi Electric Starmex R32 MXY-2H20VF System 2 outdoor condenser, LED1 (Red) blinking twice while LED2 (Yellow) remains continuously lit indicates defrosting in cooling mode while the outdoor unit continues operating (Page 7, No. 18). Mitsubishi Electric states this symptom does not indicate a product abnormality, but reflects anti-freeze modulation. Technician reference: Technician only: Per Page 7 (No. 18) of the Mitsubishi Electric service guide, inspect and wash clogged indoor air filters, check whether cold supply air is short-cycling back into the return grille, and have a technician verify R32 refrigerant pressure if evaporator icing recurs. | Source ↗ |
| LED1-LIT-LED2-2X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power System & Stop Valve Interlock (LED1 Red Lit / LED2 Yellow 2× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Power System / Compressor Wire / Stop Valve) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks twice indicates an outdoor power system abnormality when the outdoor unit does not operate (Page 8, No. 2). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes and verify that all brass liquid and gas service stop valves are fully open; have a licensed technician check the connection of the U/V/W compressor connecting wire and test the inverter P.C. board and compressor windings per Page 8 (No. 2) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-4X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Fin & Control P.C. Board Temperature Thermistor (LED1 Red Lit / LED2 Yellow 4× Blink) | Critical — Outdoor Unit Does Not Operate (Fin Thermistor or Control PCB Thermistor Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 4 times indicates a heatsink fin temperature thermistor fault or a P.C. board temperature thermistor fault on the control board, preventing outdoor unit operation (Page 8, No. 4). Technician reference: Technician only: Isolate the outdoor mains breaker for 5 minutes; have a technician check the outdoor heatsink fin thermistor harness and resistance, and if the on-board P.C. board temperature thermistor is faulty, replace the outdoor control P.C. board per Page 8 (No. 4) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-7X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Control System P.C. Board (LED1 Red Lit / LED2 Yellow 7× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Control P.C. Board Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 7 times indicates an outdoor control system abnormality on the outdoor control P.C. board, preventing outdoor unit startup (Page 8, No. 7). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes to reset the microcontroller and inspect all ribbon/wire harnesses on the outdoor control P.C. board; if LED1 Lit + LED2 7-blink persists on power-up, replace the outdoor control P.C. board per Page 8 (No. 7) of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-LIT-LED2-13X | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Current Sensor Circuit (LED1 Red Lit / LED2 Yellow 13× Blink) | Critical — Outdoor Unit Does Not Operate (Outdoor Power PCB Current Sensor Fault) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) remaining continuously lit while LED2 (Yellow) blinks 13 times indicates an outdoor power P.C. board current sensor fault under the 'Outdoor unit does not operate' symptom class (Page 8, Table No. 11). Technician reference: Technician only: Switch off the outdoor isolator breaker for 5 minutes to allow the DC bus capacitors to discharge; if LED1 (Red) Lit + LED2 (Yellow) 13-time blink persists on power-up and the outdoor unit does not operate, replace the outdoor power P.C. board per Page 8 (Table No. 11: 'Current sensor — Replace the outdoor power P.C. board') of the Mitsubishi Electric service guide. | Source ↗ |
| LED1-1X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Primary Current Modulation Control (LED1 Red 1× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates with Frequency Drop (Primary Current Protection) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking once while LED2 (Yellow) remains continuously lit indicates that the outdoor unit is operating under primary current protection frequency modulation (Page 10, Table No. 26: 'Outdoor unit operates — Primary current protection'). As noted in the service chart, this symptom does not mean an abnormality of the product itself. Technician reference: Technician only: Because primary current protection modulates compressor frequency while the outdoor unit continues operating, perform the three official Page 10 (Table No. 26) checks: (1) check if indoor unit filters are clogged, (2) check if R32 refrigerant charge is short, and (3) check if indoor or outdoor unit air circulation is short-cycled. | Source ↗ |
| LED1-2X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Evaporator Anti-Freeze / Defrosting in Cooling Control (LED1 Red 2× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates with Frequency Modulation (Defrosting in Cooling) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking twice while LED2 (Yellow) remains continuously lit indicates defrosting in cooling operation (Page 10, Table No. 27: 'Outdoor unit operates — Defrosting in cooling'). As stated in the official chart, this symptom does not mean an abnormality of the product, but reflects protective modulation against coil icing. Technician reference: Technician only: Inspect the three official points listed under Page 10 (Table No. 27) of the Mitsubishi Electric service guide: (1) check if indoor unit air filters are clogged, (2) check if R32 refrigerant is short, and (3) check if indoor or outdoor unit airflow circulation is short-cycled. | Source ↗ |
| LED1-3X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Discharge Temperature Modulation Control (LED1 Red 3× Blink / LED2 Yellow Lit) | Moderate — Outdoor Unit Operates with Frequency Modulation (Discharge Temperature Protection) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 3 times while LED2 (Yellow) remains continuously lit indicates that the outdoor unit is operating under discharge temperature protection modulation (Page 11, Table No. 28: 'Outdoor unit operates — Discharge temperature protection'). Technician reference: Technician only: Have a licensed technician inspect the three official checkpoints listed in Page 11 (Table No. 28) of the Mitsubishi Electric service guide before discharge overheating escalates into a 3-minute stop/restart lockout (LED1 3× / LED2 Not lit, Page 9 No. 15): (1) check the refrigerant circuit and refrigerant amount, (2) check the linear expansion valve (LEV), and (3) check the outdoor thermistors. | Source ↗ |
| LED1-4X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Low Discharge Superheat Protection (LED1 Red 4× Blink / LED2 Yellow Lit) | Moderate — Outdoor Unit Operates with LEV / Superheat Modulation (Low Discharge Temperature Protection) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 4 times while LED2 (Yellow) remains continuously lit indicates low discharge temperature protection while the outdoor unit continues operating (Page 11, Table No. 29: 'Outdoor unit operates — Low discharge temperature protection'). Technician reference: Technician only: Have a licensed HVAC technician perform the two checks specified in Page 11 (Table No. 29) of the Mitsubishi Electric service guide to prevent liquid refrigerant floodback to the twin-rotary compressor: (1) check the linear expansion valve (LEV) coil and stepper seating, and (2) check the refrigerant circuit and refrigerant amount. | Source ↗ |
| LED1-5X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Condenser High-Pressure Frequency Modulation (LED1 Red 5× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates with High-Pressure Modulation (Cooling High Pressure Protection) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 5 times while LED2 (Yellow) remains continuously lit indicates cooling high pressure protection while the outdoor unit operates (Page 11, Table No. 30). As explicitly stated in the official chart, these symptoms do not mean any abnormality of the product, but indicate protective compressor modulation. Technician reference: Technician only: Perform the three official field checks specified in Page 11 (Table No. 30) of the Mitsubishi Electric service guide: (1) check if indoor unit filters are clogged, (2) check if R32 refrigerant is short, and (3) check if indoor or outdoor unit air circulation is short-cycled on the condenser ledge. | Source ↗ |
| LED1-7X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG High-Low Pressure Bypass Valve & Evaporating Temperature Drop Prevention (LED1 Red 7× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates with Bypass / Anti-Freeze Control (Cooling Evaporating Temperature Drop Prevention) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 7 times while LED2 (Yellow) remains continuously lit indicates that the High-Low Pressure bypass valve / cooling evaporating temperature drop prevention control is active while the outdoor unit operates (Page 11, Table No. 31). As stated in the official chart, these symptoms do not mean any abnormality of the product. Technician reference: Technician only: Inspect the three official field checkpoints listed in Page 11 (Table No. 31) of the Mitsubishi Electric service guide: (1) check that the indoor unit air filters are not clogged, (2) check that there is sufficient R32 refrigerant, and (3) check that indoor and outdoor unit air circulation is not short-cycled. | Source ↗ |
| LED1-8X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Cooling Evaporating Temperature Protection (LED1 Red 8× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates Under Evaporating Temperature Protection (Normal Anti-Freeze Modulation) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 8 times while LED2 (Yellow) remains continuously lit indicates cooling evaporating temperature protection while the outdoor unit operates (Page 11, Table No. 32). The official service manual explicitly states: 'This symptom does not mean any abnormality of the product.' Technician reference: Technician only: Do not replace the outdoor P.C. board when LED1 blinks 8 times with LED2 continuously lit (which is normal evaporating temperature protection per Page 11, Table No. 32); distinguish this carefully from LED1 Lit + LED2 8× (current sensor fault) and LED1 8× + LED2 Not lit (converter protection 3-minute restart loop). Clean indoor filters and verify unobstructed indoor fan airflow if coil temperatures remain low. | Source ↗ |
| LED1-9X-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Inverter Check Mode Indication (LED1 Red 9× Blink / LED2 Yellow Lit) | Advisory — Outdoor Unit Operates in Inverter Check Mode (Diagnostic Status Indication) | On Mitsubishi Electric Starmex R32 MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, and MXY-5H48VG multi-split outdoor condensers, LED1 (Red) blinking 9 times while LED2 (Yellow) remains continuously lit indicates that the outdoor unit is operating in Inverter check mode (Page 11, Table No. 33: 'Outdoor unit operates — Inverter check mode'). Technician reference: Technician only: Distinguish LED1 (Red) 9× + LED2 (Yellow) Lit (Page 11, Table No. 33: 'Inverter check mode' while outdoor unit operates) from LED1 (Red) 9× + LED2 (Yellow) Not lit (Page 10, Table No. 20: 'Bus-bar voltage protection' 3-minute stop/restart loop). When verifying compressor output in inverter check mode, ensure the compressor lead connector is firmly seated and return the unit to normal operation (LED1 Lit + LED2 Lit, Page 11 No. 34) after testing. | Source ↗ |
| MUY-LED-1X-OPERATES | MUY-GP10/13/18/20/24VF Outdoor Inverter — Frequency Drop by Current Protection (Table No. 17) | Low / Normal Modulation — Outdoor Unit Operates with 1-Time Blink / 2.5s OFF | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 1 time with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 17) indicates compressor frequency drop by current protection. Technician reference: Technician only: Per Page 4 (Table No. 17), the unit is operating normally under active current-limiting modulation, but check: (1) if indoor air filters are clogged, (2) if refrigerant is short, and (3) if indoor or outdoor unit air circulation is short-cycled. | Source ↗ |
| MUY-LED-3X-OPERATES | MUY-GP10/13/18/20/24VF Outdoor Inverter — Frequency Drop by Defrosting in COOL Mode (Table No. 18) | Low / Normal Modulation — Outdoor Unit Operates with 3-Time Blink / 2.5s OFF | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 3 times with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 18 — distinct from Table No. 10 3-minute restart loop) indicates compressor frequency drop by defrosting (anti-freeze protection) in COOL mode. Technician reference: Technician only: Per Page 4 (Table No. 18), the unit is operating normally under evaporator anti-freeze protection, but check: (1) if indoor air filters are clogged, (2) if refrigerant is short, and (3) if indoor or outdoor unit air circulation is short-cycled. | Source ↗ |
| MUY-LED-4X-OPERATES | MUY-GP10/13/18/20/24VF Outdoor Inverter — Frequency Drop by Discharge Temperature Protection (Table No. 19) | Moderate — Outdoor Unit Operates with 4-Time Blink / 2.5s OFF (Active Superheat Throttling) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 4 times with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 19) indicates compressor frequency drop by discharge temperature protection. Technician reference: Technician only: Per Page 4 (Table No. 19) of the Mitsubishi Electric service manual, check: (1) the refrigerant circuit and R32 refrigerant amount, (2) the outdoor linear expansion valve (LEV), and (3) the outdoor thermistors (discharge/coil R-T resistance). | Source ↗ |
| MUY-LED-5X-OPERATES | MUY-GP10/13/18/20/24VF Outdoor Inverter — Outside Temperature Thermistor Protection (Table No. 20) | Moderate — Outdoor Unit Operates with 5-Time Blink / 2.5s OFF | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 5 times with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 20 — distinct from Table No. 12 3-minute high-pressure restart loop) indicates outside temperature thermistor protection. Technician reference: Technician only: Per Page 4 (Table No. 20) of the Mitsubishi Electric service manual, check the outdoor thermistors (ambient and outdoor coil NTC thermistor resistance and inverter P.C. board connector seating). | Source ↗ |
| MUY-LED-7X-OPERATES | MUY-GP10/13/18/20/24VF Outdoor Inverter — Low Discharge Temperature Protection (Table No. 21) | Moderate — Outdoor Unit Operates with 7-Time Blink / 2.5s OFF (Liquid Floodback Guard) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 7 times with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 21) indicates low discharge temperature protection. Technician reference: Technician only: Per Page 4 (Table No. 21) of the Mitsubishi Electric service manual: (1) check the outdoor linear expansion valve (LEV) coil and stepper valve body, and (2) check the refrigerant circuit and R32 refrigerant amount. | Source ↗ |
| MUY-LED-8X-OPERATES | MUY-GP10/13/15/18/20 PAM Protection & MUY-GP24 Zero Cross Detecting Circuit (Table No. 22) | Low / Power-Quality Modulation — Outdoor Unit Operates with 8-Time Blink / 2.5s OFF | On Mitsubishi Electric Starmex R32 single-split outdoor units, an outdoor inverter LED blinking 8 times with 2.5 seconds OFF while the outdoor unit continues operating (Symptom: "Outdoor unit operates", Page 4, Table No. 22) indicates PAM (Pulse Amplitude Modulation) protection on MUY-GP10/13/15/18/20VF (not a unit malfunction; activated by an instantaneous power voltage drop / short-time power failure or high power supply voltage) or Zero Cross Detecting Circuit activation on MUY-GP24VF (instantaneous power voltage drop or distortion of primary voltage). Technician reference: Technician only: Per Page 4 (Table No. 22) of the Mitsubishi Electric service manual, verify 230V AC 50Hz mains power supply stability, check for voltage sags/swells or primary waveform distortion at the outdoor isolator, and inspect L/N terminal tightness. | Source ↗ |
| MUY-LED-9X-OPERATES | MUY-GP10/13/18/20/24VF Single-Split Outdoor Unit — Inverter Check Mode (Page 4, Table No. 23) | Moderate — Outdoor Unit Operates in Inverter Check Mode (9-Time Blink / 2.5s OFF) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), an outdoor inverter LED blinking 9 times with 2.5 seconds OFF while the outdoor unit operates (Symptom: "Outdoor unit operates", Page 4, Table No. 23) indicates active inverter check mode. Technician reference: Technician only: Per Page 4 (Table No. 23) of the Mitsubishi Electric service manual: (1) check if the connector of the compressor is correctly connected, and (2) check the outdoor inverter P.C. board and compressor. | Source ↗ |
| LED1-LIT-LED2-8X-RESTART | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Current Sensor Protection (Page 10, Table No. 23) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red Lit / LED2 Yellow 8× Blink) | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) lit and LED2 (Yellow) blinking 8 times (Page 10, Table No. 23 — distinct from Page 8 Table No. 8 non-operating lockout), the unit has tripped on current sensor protection. Technician reference: Technician only: Isolate 230V AC power at the outdoor isolator; per Page 10 (Table No. 23) of the Mitsubishi Electric service manual, replace the outdoor power P.C. board. | Source ↗ |
| LED1-LIT-LED2-11X-RESTART | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Inter-Board Communication Protection (Page 10, Table No. 24) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red Lit / LED2 Yellow 11× Blink) | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) lit and LED2 (Yellow) blinking 11 times (Page 10, Table No. 24 — distinct from Page 8 Table No. 9 non-operating lockout), the unit has tripped on communication between P.C. boards protection. Technician reference: Technician only: Isolate 230V AC power; per Page 10 (Table No. 24) of the Mitsubishi Electric service manual, check and reseat the connecting wire harness between the outdoor control P.C. board and the outdoor power P.C. board. | Source ↗ |
| LED1-LIT-LED2-12X-RESTART | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Power P.C. Board Zero Cross Detecting Circuit (Page 10, Table No. 25) | High — Outdoor Unit Stops & Restarts 3 Minutes Later Repeatedly (LED1 Red Lit / LED2 Yellow 12× Blink) | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when the outdoor unit stops and restarts 3 minutes later repeatedly with LED1 (Red) lit and LED2 (Yellow) blinking 12 times (Page 10, Table No. 25 — distinct from Page 8 Table No. 10 non-operating lockout), the unit has tripped on the zero cross detecting circuit on the outdoor power P.C. board. Technician reference: Technician only: Isolate 230V AC power at the outdoor isolator; per Page 10 (Table No. 25) of the Mitsubishi Electric service manual, replace the outdoor power P.C. board. | Source ↗ |
| MUY-LED-1X-LOCKOUT | MUY-GP10/13/18/20/24VF Single-Split Outdoor Power System, Serial Signal & Recall Check (Page 2, Table Nos. 1, 4 & 6) | High — Outdoor Unit Does Not Operate (1-Time Blink Every 2.5s) | On Mitsubishi Electric Starmex R32 single-split outdoor units (MUY-GP10, 13, 18, 20, 24VF), when the outdoor unit does not operate and the outdoor inverter LED blinks 1 time every 2.5 seconds (Page 2, Table Nos. 1, 4 & 6 — distinct from Page 4 Table No. 17 where the outdoor unit continues operating), the fault corresponds to Outdoor Power System (No. 1), Serial Signal (No. 4), or Other Abnormality (No. 6). Technician reference: Technician only: Per Page 2 (Table Nos. 1, 4 & 6) of the Mitsubishi Electric service manual: (1) check S1/S2/S3 miswiring and serial signal error, (2) check that both liquid and gas stop valves are open, (3) check the inverter P.C. board and compressor, and (4) run the outdoor unit failure mode recall function. | Source ↗ |
| MXYH-LED1-LIT-LED2-LIT | MXY-3H28VG / 4H33VG / 4H38VG / 5H48VG Outdoor Control & Power P.C. Board Normal Status (Page 11, Table No. 34) | Normal Operation — Both LED1 (Red) & LED2 (Yellow) Continuously Lit | On Mitsubishi Electric Starmex R32 multi-split outdoor units (MXY-3H28VG, MXY-4H33VG, MXY-4H38VG, MXY-5H48VG), when both LED1 (Red) and LED2 (Yellow) remain continuously lit (Symptom: "Outdoor unit operates normally", Page 11, Table No. 34), the outdoor inverter and refrigerant system are operating normally with no active fault or frequency-drop protection. Technician reference: Technician only: Per Page 11 (Table No. 34) of the Mitsubishi Electric service manual, no repair is required when both LED1 and LED2 are steadily lit; verify normal suction/discharge operating pressures and clean indoor filters during routine servicing. | Source ↗ |
| MXY2H-LED1-LIT-LED2-LIT | MXY-2H20VF System 2 Outdoor Inverter P.C. Board — Normal Operation Status (Page 7, Table No. 25) | Normal Operation — Both LED1 (Red) & LED2 (Yellow) Continuously Lit | On the Mitsubishi Electric Starmex R32 MXY-2H20VF 2-room multi-split outdoor condenser, when both LED1 (Red) and LED2 (Yellow) remain continuously lit (Symptom: "Outdoor unit operates normally", Page 7, Table No. 25), the System 2 outdoor inverter and refrigerant cycle are operating normally with no active fault. Technician reference: Technician only: Per Page 7 (Table No. 25) of the Mitsubishi Electric service manual, no repair is required when both LED1 and LED2 are steadily lit; verify normal operating pressures and clean indoor filters during routine maintenance. | Source ↗ |